Ground Rules: Digging for the Perfect Electrical Conduit Depth

Buried Electrical Conduit

Toolup |

How Deep Should Electrical Conduit Be Buried?

Have you ever found yourself knee-deep in a trench, shovel in hand, only to realize you’re not quite sure how deep to bury the electrical conduit you're placing? 

It’s like building a bridge without knowing the weight it needs to support—things might collapse under pressure, especially if you go by questionable information or memory. 

Whether you're in the middle of a backyard project or working on a construction site, getting the right depth for your electrical conduit is the most important part. It's not just about keeping the wires safe from erosion but also about avoiding code violations or other hazards and ensuring everything works smoothly down the line for a long time.

When electrical conduits are buried at the correct depth, they’re protected from physical damage, environmental hazards, and accidental human contact, which overall prevents issues like electrical shorts, wide power outages, and potentially dangerous fires.

Failing to bury the conduit at the recommended depth can lead to serious consequences. 

Shallow conduits are more vulnerable to damage from digging or heavy machinery equipment. Additionally, not adhering to NEC code requirements can result in violations, fines, and failed inspections.

In this guide, we'll dig into the specifics of how deep to bury your conduit so you can keep your work on track and your wiring well-protected.

Call Before You Dig

Before getting too far into the details, one thing must be stressed: Call before you dig! In the U.S., this means dialing 811 or visit this website 811 In Your State, which is national hotline that will connect you to utility services in your area. They’ll send someone out to mark any underground lines, including gas, water, or electrical, to prevent accidental damage.

Accidentally hitting a utility line can lead to outages, dangerous situations, and potentially massive fines. Taking a couple of minutes to call 811 will save you from a lot of trouble—and potentially some very angry neighbors.

811 call before you dig poster

How Deep Should Electrical Conduit Be Buried?

Let’s get straight to the point of what you're here for. 

According to general guidelines from the National Electrical Code (NEC) Article 300.5(A), liquid-tight conduits like LFMC or LFNC need to be buried at least 24 inches deep. 

However, this is just a standard starting point. Electrical conduit depth requirements can vary based on factors like location, climate, and the type of conduit being used. We'll break this down step by step further down the article to give you a clear understanding of what’s required and why.

Why is Buried Electrical Conduit Depth Important?

Buried Electrical Conduit System

The importance of burying electrical conduit properly is about protecting both anyone working around it and the wire itself.

Electrical wiring, in general, is vulnerable to the environment, including wind damage, moisture, and extreme hot or cold temperatures. If left exposed, these wires will be damaged, leading to possible catastrophic power outages, death, costly repairs, or even fires. 

Burying conduit offers a layer of safety, ensuring wiring is protected from the elements, physical damage, or accidental contact.

It's important to understand the burial conditions depending on where you live though, because not every region has the same conditions. 

In places like Alaska, Minnesota, and parts of Canada, for example face extreme cold during the winter. Deep ground freezes can change the depth at which both pipes and conduit must be buried. In such cases, deeper burial might be necessary to ensure that the wiring remains protected year-round.

Understanding Electrical Conduit

Man working with buried electrical conduit

What is electrical conduit, and why is it used? 

Simply put, electrical conduit is a tube that houses electrical wiring and protects it from the environment and possible physical damage from outside forces. It's made from a variety of materials, including metal and plastic, and comes in several different sizes.

Some conduits are flexible, while others are rigid. Each type of electrical conduit has its own applications, advantages, and disadvantages depending solely on the environment being installed in.

The NEC has strict regulations on how conduit can be used, including the maximum number of wires allowed inside of it and the number of bends it's allowed to have. When planning an installation, pulling wire through conduit becomes much easier when you have fewer bends and more space inside the conduit.

In need of a cable puller? Check out Greenlee G6 Turbo 6000 lb Cable Puller

Key Benefits of Conduit

  1. Protects cables/wires against moisture, heat, and corrosion: Conduit is meant to act as a barrier by shielding wires from environmental elements that cause wear and tear over time.
  2. Prevents electrical shocks and fires: When conduit is properly installed, it can help to prevent short circuits and reduce the risk of electrical shocks or fire.
  3. Organizes wiring: By organizing wires and having them neatly routed through conduit makes future troubleshooting and repairs easy for electricians.

Factors Influencing Burial Depth

PVC electrical conduit buried underground

The depth at which electrical conduits must be buried can vary depending on a range of factors, including:

  1. Location: Different regions have specific soil conditions, frost levels, and local building codes. For example, in areas with rocky soil, it might be more difficult to achieve the required depth, while regions with extreme cold may require deeper burial to avoid frost reaching the cables.

  2. Type of conduit: Flexible non-metallic conduit (LFNC) and liquid-tight flexible metal conduit (LFMC) are popular choices for burial because of their resistance to moisture and corrosion. However, the specific type of conduit you use will also determine how deep it needs to be buried.

  3. Local building codes: These codes ensure the safety and reliability of electrical installations. Always check with your local authorities to determine the specific burial depth required for your area.

Recommended Burial Depths for Different Conditions

As mentioned earlier, the general rule for burying conduit is a depth of 24 inches. But this can change based on the location and the type of project. 

Here’s a more detailed look at different conditions and their corresponding burial depths:

  1. Under driveways or concrete slabs: Conduit only needs to be buried 18 inches deep in these situations. The added protection from the concrete reduces the risk of damage from digging or heavy machinery.

  2. Areas with heavy frost: Regions that experience deep ground freezes might require deeper burial to avoid the conduit being damaged by frost heave. In some cases, conduit might need to be buried as deep as 30 inches or more.

  3. Low-voltage wiring: For low-voltage systems (30 volts or less), such as landscape lighting, conduit only needs to be buried 6 inches deep.

  4. Direct-burial cables: If you’re using cables rated for direct burial, the depth can also vary. Low-voltage direct-burial cables should be buried at least 6 inches deep, while standard electrical wiring should be buried at 24 inches.

Common Types of Conduit

PVC Conduit buried underground

Electrical conduit comes in different options, and each one is made for specific applications. 

Here’s a brief overview of some of the most common types you'll see in underground electrical cable installation:

  1. PVC conduit: Lightweight, inexpensive, and corrosion-resistant, PVC conduit is among one of the most popular choices for outdoor and underground applications. It’s also easy to work with.

  2. LFMC (Liquidtight Flexible Metal Conduit): This type of conduit has a flexible metal core covered in a liquid-tight plastic jacket. It’s specifically for areas where you may need more flexibility around the wires and protection from moisture, such as outdoor or underground installations.

  3. LFNC (Liquidtight Flexible Nonmetallic Conduit): Similar to LFMC, but non-metallic, this type of conduit is also another type of conduit that is flexible and water-resistant. This conduit is commonly used for outdoor lighting and other outdoor installations where exposure to the elements is a concern.

  4. EMT (Electrical Metallic Tubing): Also known as “thin-wall” conduit, EMT is made from steel or aluminum and is one of the conduits most commonly used in commercial buildings. This conduit is not suitable for burial unless you have other types of protection within the conduit or around the wires.

Planning Your Installation

Once you’ve determined the type of conduit you’ll be using and the required burial depth, it’s time to start planning the actual installation. Here are a few tips to keep in mind:

  1. Straight shots are better: Fewer bends in the conduit make pulling wire much easier.

  2. Allow for future upgrades: It's also a good idea to install a larger conduit than you think you’ll need. This gives you the flexibility to add more wires, upgrade, or fix the system later.

  3. Measure twice, bury once: Double-check your measurements before digging and cutting! Don't do more work than you have to.

Installing the Conduit

Once you have dug the trench, you can lay the conduit in place. Making sure that the bottom of the trench is smooth and free from sharp rocks or sticks that could possibly damage the conduit is an important step. If necessary, add a layer of sand or pea gravel to create a stable base.

Before you backfill the trench, make sure to inspect the conduit for kinks or bends that should not be there. Once everything looks good, carefully backfill the trench, making sure to tamp the soil down to prevent settling.

What is the National Electrical Code?

The National Electrical Code (NEC) is a set of safety standards for electricians. It’s a guidebook on how to minimize the risk of electrical hazards that could cause death or serious harm and other hazards. The NEC provides specific guidelines on everything from conduit size and material to burial depths and installation methods and more. 

Beware that these guidelines are updated regularly to reflect new technologies and safety findings.

Following NEC guidelines is required by law in most areas. Failing to adhere to NEC standards can lead to fines, failed inspections, and even lawsuits in the event of an accident.

Want to look through the NEC book yourself? 

Check out this link and get free access by following the steps referenced.

Free access NFPA codes and standards

Understanding NEC Article 300.5

NEC Article 300.5 provides specific guidelines for the minimum burial depth of electrical conduits. It includes a detailed table that outlines the required depths for different types of conduit, wire, and voltage levels.

Here’s a quick breakdown of the minimum burial depths for common residential installations:

  1. 120V circuits in conduit – Minimum depth: 18 inches.

  2. 120V circuits without conduit (direct burial) – Minimum depth: 24 inches.

  3. Low-voltage landscape wiring – Minimum depth: 6 inches.

  4. Direct burial cables – Minimum depth: 24 inches.

Depth for direct burial cables or conductors:

  1. General requirement: 24 inches.

  2. Below a 2-inch thick concrete trench: 18 inches.

  3. Under streets, highways, or driveways: 24 inches.

  4. Under residential driveways or outdoor parking for dwelling-related purposes: 18 inches.

  5. In solid rock with 2 inches of concrete cover: 2 inches.

Rigid metal conduit (RMC) or intermediate metal conduit (IMC):

  1. General requirement: 6 inches.

  2. Below a 2-inch thick concrete trench: 6 inches.

  3. Under streets, highways, or driveways: 24 inches.

  4. Under residential driveways or outdoor parking for dwelling-related purposes: 18 inches.

  5. In solid rock with 2 inches of concrete cover: 2 inches.

Nonmetallic raceways listed for direct burial without concrete encasement:

  1. General requirement: 18 inches.

  2. Below a 2-inch thick concrete trench: 12 inches.

  3. Under streets, highways, or driveways: 24 inches.

  4. Under residential driveways or outdoor parking for dwelling-related purposes: 18 inches.

  5. In solid rock with 2 inches of concrete cover: 2 inches.

Residential branch circuits (120 volts or less) with GFCI protection and 20-ampere overcurrent protection:

  1. General requirement: 12 inches.

  2. Below a 2-inch thick concrete trench: 6 inches.

  3. Under streets, highways, or driveways: 24 inches.

  4. Under residential driveways or outdoor parking for dwelling-related purposes: 12 inches.

Circuits for control of irrigation and landscape lighting (30 volts or less):

  1. General requirement: 6 inches.

  2. Below a 2-inch thick concrete trench: 6 inches.

  3. Under streets, highways, or driveways: 24 inches.

  4. Under residential driveways or outdoor parking for dwelling-related purposes: 18 inches.

Check out this informative video below by Ryan Jackson for more in-depth explanations of Table 300.5

Stay Grounded and Get It Right the First Time

Proper burial depth for electrical conduit isn’t just about staying within code—it’s about ensuring that your project is safe and properly installed to last for years without problems.

From preventing damage to avoiding costly fines, knowing the right depth for your conduit can save you a lot of headaches down the line. 

Whether you’re burying conduit in rocky soil or dealing with frost in colder climates, taking the time to do it right pays off. 

So, before you grab that shovel and dig that trench, make sure you’ve done your homework, and you've measured twice. Your future self will thank you for it.

Buried Electrical Conduit Depth Frequently Asked Questions

What is the minimum burial depth for an electrical conduit?

The general rule is that electrical conduit needs to be buried at least 18 to 24 inches deep, depending on the type of conduit and the specific installation conditions. Under driveways or slabs, 18 inches is sufficient, while in open ground, 24 inches is typical. Always refer to NEC guidelines for exact requirements based on the type of conduit and voltage level.

What happens if the conduit is buried too shallow?

If an electrical conduit is buried too shallow, it’s more prone to damage from digging, environmental factors like freezing and thawing, or heavy machinery passing over it. Shallow burial increases the risk of physical damage to the conduit, leading to electrical faults, outages, or safety hazards like electrocution.

Do I need to use conduit for underground electrical wiring?

Conduit isn't required for underground wiring if you're using direct-burial cables rated for such use. However, running wiring through conduit provides extra protection, especially in areas with harsh environmental conditions or heavy traffic. Conduit also makes future upgrades or repairs easier since you won’t have to dig up the wiring.

What are the NEC requirements for conduit burial?

NEC Article 300.5 provides the guidelines for burial depth and conduit installation. It outlines the minimum depth for different types of conduit, depending on voltage level, conduit type, and location. For standard electrical conduits in open ground, the minimum burial depth is 24 inches, while low-voltage wiring can be buried 6 inches deep.

What is the difference between direct burial cable and conduit?

Direct burial cable is rated for burial without additional protection, while conduit houses electrical wires for added protection. Direct burial cables are typically used for specific outdoor or underground applications, but conduit offers more flexibility for future upgrades and better protection in harsher environments.